Power & Distribution Transformer

Output Voltage 0.433 KV (As Per Customer’s Demand)
Phase Three Phase
Brand KAY PEE
Input Voltage 11 KV & 22 KV & 33 KV (As Per Customer’s Demand)
Frequency 50 HZ
Winding Material E. C. Grade D. P. C. Copper Wire & Strips
Class Of Insulation A
Orientation Of HV and LV 180 Degree (As Per Customer’s Demand)
Temprature Rise Oil and Winding 40 DegreeC (In Oil) & 45 DegreeC (In Winding)
Taping As Per Customer’s Demand
Impedance As Per BIS
No load Current Less Than 2 % Of Full Load Current
No Load Losses As Per Customer’s Demand
Full Load Losses As Per BIS Level
Load Losses At Half Load As Per BIS Level
Rated Capacity As Per Customer’s Demand
No Of Phase Three
Installaton Indoor / Outdoor
Vector Groupe As Per Customer’s Demand
Type Of Cooling Oil Cooled

Description

” KAY PEE ” Offers A Complete Range Of Power & Distribution Transformers Designed To Grant The Reliability , Durability & Efficiency Required In Utility , Industrial & Commercial Applications. KAY PEE’s Liquid Filled Transformers Are Manufactured In Accordance With The Most Demanding Industry & International Standards. Transformers Can Be Used For Indoor OR Outdoor Applications & Can Be Provided With Off Load & On Load Tape Changers.

The Transformer Are manufactured in accordance with IS 2026/1977, IS 1180/2016, IEC 60076 or as per customer’s custom requirement.

The transformers will be suitable for outdoor installation with three phase, 50Hz, 11 kV system in which the neutral is effectively earthed and theyshould be suitable for service with fluctuations in supply voltage up to plus 12.5% to minus 12.5%.


Range :
 The standard ratings shall be 250, 315, 400, 500, 630, 800, 1000, 1250, 1500, 1600, 2000 and 2500 KVA for 11 kV distribution transformers.


Vector Group 
As per customer’s custom requirement.

Core :
 The core shall be stack / wound type of high grade cold rolled grain oriented annealed steel lamination having low loss and good grain properties, coated with hot oil proof insulation, bolted together and to the frames firmly to prevent vibration or noise.

Core Test 
The preliminary core loss test will be conducted before passing to the assembly stage.

Winding : 
HV and LV windings shall be wound from Super Enamel covered /Double Paper covered, aluminum /copper conductor/ foil.

Tapings : 
For ratings higher than 250 kVA, tapping shall be provided if required by the purchaser on the higher voltage winding for variation of HV voltage within range of (+) 5.0 % to (-)15.0 % in steps of 2.5%.

OIL :
 The insulating oil shall comply with the requirements of IS 335 or BS 148 Oil shall be filtered and tested for break down voltage (BDV) and moisture content before filling. The oil shall be filled under vacuum.

Tank :
The transformer tank is of robust construction rectangular in shape and shall be built up of electrically tested welded mild steel plates of thickness of 6 mm for top and bottom and 4 mm side plate.

Conservator : 
The capacity of a conservator tank is designed keeping in Observation the total quantity of oil and its contraction and expansion due to temperature variations The total volume of conservator shall be such as to contain10% quantity of the oil. Normally 3% quantity the oil shall be contained in the conservator.

BUSHINGS:
 for 11 kV, 17.5 kV class bushings and for 0.433 kV, 1.1 kV class bushings shall be used.

TESTING : We are conduct all routin test.